The XP95 mains switching input/output unit provides a voltage free single pole change-over relay output and a monitored switch input. Designed for use with the XFP addressable single and two loop fire alarm panels, the mains switching input/output unit is supplied with a surface mounting back box and is suitable for indoor use only.
Product Code | FLAPXP123 |
---|---|
Alternative Product Codes | 4700-103, SA4700-103APO, AP2518M |
Brand | Apollo |
Dimensions | 150x90x48mm |
Manufacturer Part Number | SA4700-103APO |
Maximum Current Consumption at 24V | Switch-on surge, max 150ms: 3.5mA LED enabled, 3.5mA LED disabled Quiescent, 20k? EOL fitted: 1.25mA LED enabled, 1.2mA LED disabled Switch input closed LED on: 2.5mA LED enabled, 1.5mA LED disabled |
Operating Temperature | -20°C to +70°C |
Operating Voltage | 17-28V DC |
Relative Humidity | 0% to 95% (non condensing) |
Switch Input Monitoring Voltage | 9-11V DC (open-circuit condition) |
Weight | 0.24kg |
Product Datasheets |
Model | Stock | Price |
---|---|---|
Product Code: FLAPXP123 |
Stock Level:
Available for pre-order Expected dispatch: 4th Jul
|
Price:
£74.03 inc VAT £61.69 ex VAT |
The following delivery options are available on this product.
If you have any questions or would like more information about this product you can ask one of our specialists.