Array ( [name] => BritanniaBottom [title] => 3 Simple Step Maintenance Process [content] =>
P50 extinguishers can be visually inspected easily by any person following the manufacturer's simple visual inspection instructions. The annual visual check is then simply recorded on the back of the extinguisher (using a permanent marker) and in the company's fire log book.
Visually inspect the extinguisher, checking for any signs of tampering or damage and ensure that the tamper seal is still in place. Using a clean cloth remove any dust and dirt that may have built up on the extinguisher's body.
Check the manufacturing date of the extinguisher, this is either indicated by the coloured plug in the side of the nozzle holder or printed on the underneath of the extinguisher.
Visually check that the needles in both pressure indicators are in the green. Hold a magnet underneath the front pressure indicator (located directly under the safety pin) and move it from side to side so that the needle follows it. Release the magnet and ensure that the needle returns to the green area of the indicator.