Foam fire extinguishers supplied by Safelincs have passed a di-electrical test according to BS EN3-7 clause 9. The conductivity of a fire extinguisher is tested by monitoring the current at 35kV before and during the extinguisher discharge. To pass the test the required current at 35kV needs to be less than or equal to 0.5mA. Each foam fire extinguisher tested has demonstrated compliance with this.